GAOTek Partial Discharge Tester

The Partial Discharge Tester is based on the experience of many years of partial discharge test and is suitable for on-line detection and positioning of partial discharge of high voltage equipment.

SKU: GAOTek-LTP-190 Category:
Description

Description

Overview

The Partial Discharge Tester is based on the experience of many years of partial discharge test and is suitable for on-line detection and positioning of partial discharge of high voltage equipment. The system is equipped with a composite TEV sensor, ultra-high frequency sensor, high-frequency current transformer and high-sensitivity ultrasonic sensor to collect partial discharge signals inside the high-voltage equipment. The system adopts multi-stage detection and frequency reduction technology to reduce the frequency of the discharge signal. At the same time, the high-speed AD conversion circuit is used to complete the digitization of the signal, and the reliability of the detection data is ensured by the interference signal processing methods such as digital signal processing and adaptive filtering. The fast-running detection of the operating state of the device can be performed by collecting different signals generated by partial discharges in different high voltage devices. The instrument can be installed and tested under the operating condition of the equipment and has no impact on the normal operation of the equipment. It is convenient for the staff to evaluate the operating status of the switch cabinet in time, which improves the reliability, safety, and effectiveness of the equipment operation. The hand-held multifunctional partial discharge tester consists of a tester host, a TEV sensor, an ultrasonic sensor, a high-frequency current transformer, an ultra-high frequency sensor, and a connecting line.

 

Features

  • The system adopts multistage detection
  • Frequency reduction technology
  • High-speed AD conversion circuit
  • Used to complete the digitization of the signal
  • Reliability of the detection data is ensured
  • Digital signal processing and adaptive filtering
  • Fast running detection
  • Has no effect on the normal operation of the equipment

 

Technical Specifications

Accuracy ± 1DB
Display LED Display and Ability to Display Battery Status
Certification ISO
Pulse Or Cycle Maximum 655
Resolution 1DB
Detection Bandwidth 5 MHz to 70MHz
Threshold Adjustment Range 3 dB to 57 dB
Sensor Capacitive
Measuring Range 0 DBmV to 60 dBmV
Resolution Ratio 1DB
Detection Frequency Band 10 kHz to 30 MHz
Signal Transmission Mode 50 Ω Coaxial Cable
Detection Sensitivity 10 PC
Gain > 65 Dbm
Altitude ≤ 3000 m
Relative Humidity ≤ 95 %
Use Temperature -4 ºF to 140 ºF (-20 ºC to 60 ºC)