High-Precision 8-Ch Analog Input Ethernet Remote I/O Module 16-Bit – GAOTek

GAOTek’s high-precision 8-Ch analog input ethernet remote I/O module 16-Bit is an industrial-grade, high-reliability, and high-precision data acquisition solution.

SKU: GAOTek-AIERM-101 Category:
Description

Description

Overview

GAOTek’s high-precision 8-Ch analog input ethernet remote I/O module 16-Bit is an industrial-grade, high-reliability, and high-precision data acquisition solution. It is embedded with a 32-bit high-performance microprocessor MCU and integrates an adaptive 10/100M industrial Ethernet port. This device supports Modbus TCP (master and slave) and can be seamlessly integrated into SCADA, OPC servers, and other automation systems. Designed to withstand harsh industrial environments, it is widely applied in automation, monitoring, and control systems. 

 

Features

  • Standard Modbus TCP protocol, Modbus RTU over TCP protocol, and MQTT protocol; 
  • Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog; 
  • Power supply 9V to 36V DC with over voltage and phase-reversal protection; 
  • Integrated 10/100M adaptive Ethernet port, With 6KV ESD protection; 
  • Optical isolated digital input (Compatible Dry or Wet type), supports max 700KHz high speed pulse counter, The optional low-speed pulse frequency can reach up to 10 kHz. 
  • Support DIN2 to DIN12 as a low-speed pulse counter. The anti-jitter time can be set to 1ms to 2000ms, the default is 1ms, and the corresponding pulse frequency is up to 1KHz; 
  • DO supports Sink output, DO1 can be used as high-speed pulse output, supports 10Hz to 300KHz; 
  • Isolated Analog input, 16-bit resolution, supports 0A to 20mA, 4mA to 20mA, 0V to 5V DC, 0V to 10V DC; 
  • 1 RS485 Serial port, supports Modbus RTU Master/Slave, can extend I/O modules; 
  • Supports register mapping function and extend I/O inquiry strategy; 
  • Supports TCP Client and TCP Server, supports max. 5 TCP Client connections; 
  • 1 channel DC power source output for external device, saving wiring cost; 
  • Can be managed and configured via configuration software over a local area network (LAN), making it easy to operate and maintain; 
  • LED instructions work status, with reset button to reset, easy on-site installation and commissioning; 
  • Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial applications in the field. 

 

Technical Specifications

Power – Input Voltage  Without AO: 9 VDC to 36 VDC / 0.009 kVDC to 0.036 kVDC
With AO: 24 VDC to 36 VDC / 0.024 kVDC to 0.036 kVDC 
Power Consumption  ≤ 2 W (standby) 
Power Output  1 channel
Output Voltage: 9 VDC to 36 VDC (equal to input)
Output Current: 1500 mA @ 12 V (Max) = 1.5 A 
Power Protection  Reverse wiring prevention
ESD: 6 kV
Surge: 1 kV
EFT: 1 kV, 5 kHz 
Ethernet  1 × RJ45, 10/100 Mbps 
Ethernet Port Protection  ESD: 6 kV
Surge: 1 kV (8/20 μs), 3 kA
EFT: 1 kV, 5 kHz
CE: 150 kHz to 80 MHz, 3 V 
Ethernet Protocols  Modbus RTU, Modbus TCP, MQTT 
Serial Port – Quantity  1 × RS485 
Baud Rate  2400 bps to 128000 bps 
Data Bits  7, 8 
Parity Bits  None, Even, Odd 
Stop Bits  0.5, 1, 1.5, 2 
Serial Protocols  Modbus RTU (slave & master) 
Serial Protection  ESD: 6 kV
Surge: 1 kV (8/20 μs)
EFT: 1 kV, 5 kHz
CE: 150 kHz to 80 MHz, 3 V 
Digital Input – Quantity  16 channels (Max) 
Digital Input – Type  Wet contact (NPN, PNP) & Dry contact (default: Wet) 
Dry Contact  Close = Short circuit
Open = Open circuit 
Wet Contact  Close: 10 VDC to 30 VDC
Open: 0 VDC to 3 VDC 
Pulse Counter  DIN1: High-speed (up to 700 kHz) or Low-speed (up to 10 kHz)
DIN2 to DIN12: Low-speed (up to 1 kHz, adjustable anti-jitter 1–2000 ms) 
Isolation Protection  2.5 kVrms 
Sampling Rate (DI)  100 Hz 
Digital Input Protection  ESD: 6 kV
Surge: 1 kV (8/20 μs)
EFT: 1 kV, 5 kHz
CE: 150 kHz to 80 MHz, 3 V 
Digital Output – Quantity  16 channels (Max) 
Digital Output – Type  Sink 
DO Capacity  500 mA per 4 channels 
Overvoltage Protection  50 VDC 
Pulse Output  DO1: 10 Hz–300 kHz 
DO Protection  ESD: 6 kV
Surge: 1 kV (8/20 μs)
EFT: 1 kV, 5 kHz
CE: 150 kHz–80 MHz, 3 V 
Analog Input – Quantity  8 channels (Max) 
Analog Input – Type  Single-ended input: 4–20 mA, 0–20 mA, 0–5 V, 0–10 V 
Resolution (AI)  16-bit 
Accuracy (AI)  ±0.5 ‰ FSR at 25 °C 
Input Impedance  Voltage: >2 kΩ
Current: 162 Ω 
Analog Input Protection  ESD: 6 kV
Surge: 1 kV (8/20 μs)
EFT: 1 kV, 5 kHz
CE: 150 kHz to 80 MHz, 3 V 
RTD – Quantity  6 channels (Max) 
RTD Range  -58 °F to +572 °F (-50 °C to +300 °C) 
RTD Type  2/3/4 wire PT100 / PT1000 
RTD Resolution  12-bit 
RTD Accuracy  ±0.1% FSR at 25 °C
±0.3% FSR at -10 & 60 °C
±0.5% FSR at -40 & 75 °C 
RTD Sampling Rate  20 Hz 
Analog Output – Quantity  2 channels 
Analog Output – Type  0 VDC to 10 VDC, 0 mA to 20 mA, 4 mA to 20 mA (Single-ended to GND) 
Analog Output Data Type  32-bit float 
Analog Output Max Load  1000 mA (1 A) 
Analog Output Protection  ESD: 6 kV
Surge: 1 kV (8/20 μs) 
Thermocouple – Quantity  8 channels (Max) 
Thermocouple Types  B, E, J, K, N, R, S, T 
Thermocouple Accuracy  ±5.4 °F (±3 °C)  
Cold Junction Compensation  17.6 °F to 46.2 °F (-8 °C to +7.9 °C) 
Relay Spec  5 A at 250 VAC (62.5 VA)
3 A at 30 VDC (90 W) 
Software Protocols  IPv4, TCP/UDP, DNS, Modbus RTU, Modbus TCP, MQTT 
Protocol Conversion  Modbus TCP ↔ RTU
Modbus RTU ↔ MQTT
Modbus TCP ↔ MQTT 
Indicators  Power, Link, RS485_RXD, RS485_TXD, I/O Status 
User Config  PC Software (Win XP, 7, 8, 10) 
Map Data  Bool: 300, 16-bit: 300 
Login/Heartbeat Package  Custom login/heartbeat supported 
Installation  DIN-rail or Wall-mounted 
Environment – Working  -4 °F to +158 °F (-20 °C to +70 °C), 5% RH to 95% RH 
Environment – Storage  40 °F to +185 °F (-40 °C to +85 °C), 5% RH to 95% RH 
Case  Metal 
Dimensions  3.23 in × 1.57 in × 3.94 in (82 mm × 40 mm × 100 mm) 
Protection Grade  IP30 