Power Supply |
Instrument with RS485 port: 230 VACS ±15% / 115 VAC ±15% (on request) |
Voltage Inputs |
Maximum measurable voltage: 600 VAC L-L |
Current Inputs |
Maximum value: 7 A, Starting current: 2 mA |
Typical Accuracy/Performance Class |
Voltage: ±0.2% reading in 10% FS…FS range |
Network Analyzer |
DIN 96 X 96 |
Display |
Highly readable Backlit LCD Screen |
Measurement range |
600 V |
Current Input |
1 A or 5 A |
Power supply |
230 Vac or 85.265VAC /110Vdc |
Accuracy |
Class 0,5 |
Measurement |
FFT Harmonic analysis to 15th order |
Memory |
8MB. Selectable parameters for data logging |
I/O |
2 Digital outputs to 1 Digital input |
Communication |
Ethernet Rj45 (Modbus TCP) |
2 Digital Outputs (DO) |
NPN or PNP, passive opt isolated |
Maximum Values |
27 VDC to 27 mA |
Energy Pulse Length (for DO in pulse mode) |
50 ±2 ms ON time |
Max Output Reaction Time (for DO in alarm mode) |
1s |
Digital Input (DI) Type |
opt isolated |
Max Humidity (without condensation) |
80% |
Sinusoidal Vibration Amplitude |
50 Hz ± 0.020 in (0.0075 cm) |
Protection Degree (Frontal Part) |
IP54 (granted only if installed in a cabinet with at least IP54 protection degree) |
Voltage Range |
80.265 VAC-DC |
Measuring Terminals (A&V) |
2.5 mm²/14 AWG |
Terminals for I/O, AUX, RS485 Port |
1.5 mm²/16 AWG |
Operating Temperature |
-13 ℉ to 131 ℉ (-25 °C to +55 °C) |
Storage Temperature |
-13 ℉ to 167 ℉ (-25 °C to +75 °C) |
Size |
3.77 in x 3.77 in x 1.53 in (9.6 cm x 9.6 cm x 3.9 cm) |
Weight |
 10.93 oz (310 g) |