Description
Overview
GAOTek wall-mounted hf gas detector is a high performance intelligent toxic gas detection alarm which adopted Membrapor sensor from Switzerland, high performance, supply couples of types of gas detection, low power microprocessor to ensure product performance and stability, real-time monitoring of the concentration of toxic gas. Mainly used in petroleum chemical industry, metallurgy, mining, fire, gas, environmental protection, electric power, communication, papermaking, printing and dyeing, food reserves, city water supply, sewage treatment, food, brewing, research, education, national defense and other places.
Features
- Three kinds of signal output, 4 mA to 20 mA (three wire)
- Digital / analog signal and switch at the same time
- Big screen segment type LCD real-time display gas concentration
- Gas concentration unit optional (such as ppm, mg/m3)
- It has the instrument status, fault and communication abnormality prompt function
- It can be set to a high and low alarm point, two level sound and light alarm
- Two relays to control peripheral devices (such as the action of machine, sound and light alarm)
- Round casting stainless steel housing is suitable for offshore platforms, high temperature, high humidity and other harsh environments
- Good sealing, anti-corrosion, explosion-proof and anti-EMI, RFI function.
- European design standards.
Technical Specifications
Measured Gas | Toxic gas or Oxygen gas |
Sensor Type | Electro-chemical, |
Sampling Way | Diffusion, pump (pipeline) |
Detection Range | Details see sensor data |
Accuracy | Details see sensor data |
Response Time | T 90 ≤ 30 S (most) |
Display | LCD display real-time concentration, light emitting diode, buzzer alarm |
Material Of Housing | Cast aluminum |
Pressure Range | 860 hpa to 1060 hpa |
Operating Current | 20 mA to 200 mA |
Span Drift | ≤ ± 5 % FS/6 h |
Life For Sensor | See date of sensor |
Housing Color | yellow |
Explosion-Proof Grade | Exd II CT6 |
Protection Grade | IP65 |
The Power Consumption | ≤ 3 W |
Current Consumption | 20 MA to 200 MA |
Alarm Error | ≤ ± 10 % alarm set value |
Work Humidity | 0 % RH to 85 % RH (no coagulation) |
Preheating Time | 1 Min |
Signal Output | 4 mA to 20 mA, RS 485 |
Equipment Service Life | 10 years ( in the air ) |
Capacity | 0.5 A/125 V AC or 1 A/30 V DC |
Repeat | ≤ ± 2 % FS |
Zero Drift | ≤ ± 2 % FS/6 h |
Transmission Distance | 4 mA to 20 mA ≤ 100 m , RS 485 ≤1000 m |
Cable | ≥ RVVP9  x 0.3 mm2 |
Electrical Interface(Thread) | M26 x P2.0 (explosion-proof connector: M26 M20)t |
Weight | < 4.41 lb (2 kg) |
Operating Temperature | 14 °F to 104 °F (-10 ℃  to 40 ℃) |