GAOTek Low Voltage Switchgear Electrical Power Distribution Equipment Switch Cabinet
GAOTek low voltage switchgear electrical power distribution equipment switch cabinet is an intelligent low-voltage switchgear.
Description
Overview
GAOTek low voltage switchgear electrical power distribution equipment switch cabinet is an intelligent low-voltage switchgear.It is modular low-voltage switchgear. It is used for the distribution, conversion, control and reactive power compensation of indoor power distribution systems with AC 50 Hz or 60 Hz, rated operating voltage ≤690 V, rated operating current ≤6300 A. This product is suitable for applications in power plants, petrochemicals, offshore platforms, metallurgy, paper making, public facilities engineering and other occasions. The low-voltage systems provide leading solutions in the field of power distribution and motor control, and provide switch cabinets integrating power and automation for customers in the process industry, power and infrastructure industries, superior safety protection for personnel and equipment, lower operating costs, improve equipment operation availability, reliable, flexible, scalable, and easy maintenance from the front of the switchgear.
Â
Features
- Use the Rittal top-level TS8 cabinet
- Protection class IP54
- PU foam seal
- Full of elasticity
- Resistant to 356 ℉ high temperature without hardening
- The frame is welded by a unique 16-fold profile
- high strength and excellent load-bearing performance
- Surface of the cabinet treated with oil removal and phosphating
- Surface of the cabinet treated with Electrophoretic primer
- Surface of the cabinet treated with powder sprayed
- The surface of the paint has high strength
- Strong corrosion resistance
- Grease resistance
- Weak acid and alkali resistance
- Special communication to connect with intelligent equipment drawer
- Cabinet body adopts modular structure
- 98 in modular hole frame
- Easy to install
- Isolation level up to form 4b
Â
Technical Specifications
Rated Working Voltage (Ue) V | The main circuit AC 380 V, AC 690 V auxiliary circuit AC 220 V, AC 380 V, DC 110 V, DC 220 V |
Rated Insulation Voltage (Ui) V | The main circuit AC 500 V, AC 690 V |
Rated Impulse With Stand Voltage kV, 1.2 / 50 μs | Main bus 8 kV feeder circuit 6 kV |
Rated Working Current A At IP3X | Horizontal bus 1000 A, 1250 A, 1600 A, 2000 A, 2500 A, 3200 A, 3600A, 4000 A, 5000 A, 6300AVertical bus 1250 A (drawer type), 1500 A (drawer type capacity increase type), ≤ 2000 A (plug-in MCCB) |
Rated Short-Time With Stand Current, Icw, kA / 1 Second | Horizontal bus 50,80,100Vertical bus 50,80,90 |
Rated Peak Withs Stand Current, Ipk, kA / 0.1 second | Horizontal bus 105,176,220Vertical bus 105,176,198 |
Protection Class | Close the door IP3X, 42, 54 open the door IP2X |