Description
Technical Specifications
Detecting Gas | CH4/LEL CO O2 H2S(optional) CH4 |
Measurement Range | (0.00 to 5.00) % Vol |
Measurement Error | (0.00 to 1.00)% CH4: ±0.10% CH4 (1.00 to 3.00) % CH: true value±10% (3.00 TO 4.00) %CH4: ±0.30% CH4 |
Respond Time | 20S(T90) |
Resolution | 0.01% vol |
Respond Time | 20S(T90) |
Measurement Range | (0 to 00) ppm |
Measurement Error | (0 to 50) ppm: ± 3ppm (50 to 100) ppm: true value±10% |
Respond Time | ≤45S(T90) |
Resolution | 1 ppm |
Alarm Point | 10 ppm (can be adjusted in whole range) |
Alarm Sound Intensity | 80dB |
Alarm Way | Sound, light alarm |
Alarm Indicator Light | Can be visible in the distance of not less 20 m |
Sensor Life | ≥2 years (CO, O2, H2S) ≥1 years (LEL, CH4) |
Working Current | 95 mA |
Continuous Operating Hours | ≥12 hours |
Battery Item | Pl123450 3.7V/1500 mA |
Battery Short Circuit Current | 2A |
Charging Time | 4 to |
Protection Level | IP54 |
Working Temperature | -13°F to 41°F (-25℃ to 5℃) Short time for –40 °F to 131°F (-40 ℃ to 55 ℃) |
Size | 5.11 in x 2.59 in x 1.18 in (130 mm x 66 mm x 30 mm) |