Description
Technical Specifications
Ambient Conditions (For Indoor Use Only) | |
Reference Conditions | All accuracies stated at 73.4 °F ± 1.8 °F (23°C ± 1°Cz) |
Operating Temperature | 32 °F to 122 °F (0 °C to 50 °C) |
Temperature Coefficient Of Current | ≤ ± 0.15 % of rdg per °C |
Temperature Coefficient Of Voltage | ≤ ± 0.15 % of rdg per °C |
Maximum Relative Humidity | 80 % for temperatures up to 87 °F (31 °C) decreasing linearly to 50 % relative humidity at 104 °F (40 °C) |
Maximum Safe Working Voltages | Safety IEC 61010-1 600 V CAT IV double or reinforced insulation, pollution degree 2 |
Current Measurement | 600 V ac rms or dc between uninsulated conductor and ground |
Voltage Measurement | 600 V ac rms or dc between either input terminal and ground, or 825 V between energized phase voltages (delta power config.) |
Dimensions (Length x Width x Depth) | 12 in x 3.75 in x 2 in (300 mm x 98 mm x 52 mm) |
Weight Including Batteries | 1.8 lb (0.82 kg) |
Jaw Opening | 2.3 in (60 mm) |
Jaw Capacity | 2.2 in (58 mm) diameter |
Cleaning | The unit can be cleaned with an Isopropanol impregnated cloth. Do not use abrasives or other solvents. |
Current Measurement (dc, dc rms, ac rms) | |
Measuring range | 0 A to 2000 A dc or 1400 ac rms |
Auto Range Facility | 40 A or 400 A or 2000 A |
Resolution | 10 mA in 40 A range 100 mA in 400 A range 1 A in 2000 A range |
Accuracy DC and dc rms | I > 10 A: ± 1.5 % rdg ± 5 digits I < 10 A: ± 0.2 A |
Accuracy AVG | I > 10 A: ± 3 % rdg ± 5 digits I < 10 A: ± 0.5 A |
Accuracy Pk | I > 10 A: ± 5 % rdg ± 5 digits I < 10 A: ± 0.5 A |
Accuracy: Ahr | I > 10 A: ± 2 % rdg ± 5 digits I < 10 A: ± 0.5 Ahr |
Accuracy CF (Crest Factor) | 1.1 = CF < 3: ± 3 % rdg ± 5 digits 3 = CF < 5: ± 5 % rdg ± 5 digits Resolution: 0.01 |
Accuracy RPL (Ripple) | 2 % = RPL < 100 %: ± 3 % rdg ± 5 digits 100 % = RPL < 600 %: ± 5 % rdg ± 5 digits Resolution: 0.1 % Idc > 5 A, Iac > 2 A |