Description
Overview
GAOTek logger quality recorder electrical delay network analyzer is a dedicated portable product for detecting and analyzing power quality parameters. Power quality parameters include frequency, voltage or current amplitude, harmonics, inter-harmonics, unbalance, voltage flicker, power factor, etc. In addition, it can carry out long-term data collection and monitoring on the operation of the power grid. At the same time, it is equipped with power quality data analysis software to perform various analyzes on the measurement data uploaded to the computer.
Features
- Use ARM and DSP and 16 M bytes of memory
- A touch screen to make the operation easier and more convenient
- Can measure, save the data and upload it to PC for analysis
- Chinese or English menu operation, simple and easy to operate
- Software can be updated using a USB disk
Technical Specification
Voltage input | |
Input resistance | 1 MΩ, 20 pF |
Accuracy | 0.1 % rdg ± 0.05 % f.s |
Measurement range | 3-phase: true RMS 1000 VNeutral wire: true RMS 70 V |
Power consumption | < 0.5 V A per phase |
Current input | |
Measurement range | True RMS 1 A, 5 A, 10 A, 100 A, 500 A, 1000 A, 3000 A |
Accuracy | 0.2 % rdg ± 0.05 % f.s |
Power consumption | < 0.5 V A per phase |
Frequency | 40 Hz to 70 Hz |
Frequency accuracy | ± 0.01 Hz |
Power | |
Active power | 700 kW |
Reactive power | 700 kVar |
Apparent power | 700 k VA |
Electrical energy | |
Active energy | 10000 kWh |
Reactive energy | 10000 kVAh |
Apparent energy | 10000 kVARh |
Average power factor | 0.00 to 1.00 |
Measurement accuracy | ± 0.5 %, PF ± 0.005 |
Three-phase unbalance | |
Voltage fundamental | 1000 V true RMS |
Current fundamental | 6000 A true RMS |
Fundamental frequency | 40 Hz to 70 Hz |
Physical parameters | |
Display | 5.7 in LCD |
Storage | 128 M bit FLASH |
External interface | USB |
Working power supply | Rechargeable lithium battery (continually work 5 hrs to 6 hrs) |
External power supply | AC 100 V to 240 V or DC 16.8 V to 1 A |