Use environment | Input Power Supply | 220 V ± 10% 50 Hz ± 10% |
Atmospheric Pressure | 86 Kpa to 106 Kpa | |
Temperature | 14 °F to 113 °F (-10 ℃ to 45 ℃) | |
Humidity | ≤ Q 80% RH | |
Safety performance | Insulation Resistance | > 2MΩ |
Dielectric Strength | Power supply on the chassis power frequency 1.5 kV withstand voltage for 1 minute, no flashover and arcing | |
Basic parameters | Time | Range:16000.0 ms, Resolution: 0.1 ms Error: 1. within 200 ms, 0.1 ms ± 1 word 2. 200 ms or above, ± 2% 3. The same period, ± 0.1ms |
Speed | Range:20.00 m/s, Resolution 0.01 m/s error:1. within 0 m/s to 2 m/s,± 0.1 m/s ± 1 digital 2. 2 m/s or above, ± 0.2 m/s |
|
Stroke | Vacuum circuit breaker: Range: 50.0 mm Resolution: 0.1mm, error: ± 0.5 mm SF6 circuit breaker: Range: 300.0 mm,Resolution:0.1 mm error:± 2 mm Less oil circuit breaker:Range:600.0 mm,Resolution:0.1 mm error:± 2 mm |
|
Current | Range:20.00A ,Resolution:0.01A | |
Closing Resistor | Range:0 Ω to 2000Ω; Resolution:1 Ω,Precision:1% | |
Fracture Type | 12-way metal fracture, 6-way closing resistor fracture | |
Output Power Supply | DC30 V to 250 V digital adjustable / 20 A (instantaneous work) | |
Dimensions | Host:14.71 in x 11.4 in x 11 in (360 mm × 290 mm × 280 mm3): annex: 11.56 in x 11 in x 8.6 in (370 mm × 280 mm × 220 mm3) | |
Weight | Host:13.2 lb (6kg): annex:19.8 lb 9kg |