Description
Features
- Battery operated
- PASS or FAIL result
- Color status backlight
- 10 mA and 30 mA RCD test (Isolation transformer built-in)
- Memory functions up to 999 data
- Printer output
- Complies to AS, NZS 3760
Technical Specification
Main voltage indication | |||||
Display range | 30 V to 270 V | ||||
Accuracy | ± 5 V | ||||
Protective conductor resistance test | |||||
Measuring range | 0.00 Ω to 20.00 Ω | ||||
Open circuit voltage | 5 V ± 0.4 V DC | ||||
Measuring current | 200 mA DC (nominal value) | ||||
Accuracy | ± 3 % rdg ± 5 dgt | ||||
Insulation resistance test | |||||
Rated voltage | 250 V | 500 V | |||
Measuring range | 0.00 MΩ to 20.00 MΩ | ||||
No-load voltage | 250 V DC +20 %, -0 % | 500 V DC +20 %, -0 % | |||
Short circuit current | 1.5 mA DC or less | ||||
Accuracy | ± 2 % rdg ± 3 dgt | ||||
Load current or Leakage current test | |||||
Item | Load current | Leakage current | |||
Mains voltage range | 100 V to 253 V or 50 Hz | ||||
Measuring range | 0.10 A to 10.00 A rms | 0.10 mA to 20.00 mA rms | |||
Accuracy | ± 10 % rdg ± 5 dgt | ± 3 % rdg ± 5 dgt | |||
RCD test | |||||
Rated voltage | 230 V -15%Â – +10% or 50 Hz | ||||
Rated current | 10 mA or 30 mA | ||||
Function | × 1 | × 5 | |||
Test duration | 0.0 ms to 500.0 ms | 0.0 ms to 40.0 ms | |||
Operating time accuracy | ± 2 ms (<= 40 ms), ± 8 ms (> 40 ms) | ||||
General | |||||
Power source | LR6 (AA) (1.5 V) × 6 | ||||
Dimensions, Weight | 10.27 in × 4.09 in × 2.24 in (261 mm × 104 mm × 57 mm), 2.05 lb (930 g) (including batteries) |