Overview
GAOTek circuit impedance parameter tester is designed for efficient and accurate calibration of the primary measurement functions of the predominant Transformer Comprehensive Parameter Testers and Transformer No-Load Loss Parameter Testers available in the market. These primary measurement functions include no-load loss, load loss, no-load current, load current, impedance voltage, power, power factor, and frequency. The calibration device is equipped with a user interface tailored to the measurement features of the Transformer Comprehensive Parameter Tester. Users can conveniently preset relevant standard values directly, eliminating the need for additional manual conversion into corresponding current, voltage, angle values, and so on. This feature enhances the efficiency and reliability of the calibration process.
Technical SpecificationsÂ
No-Load Loss, Load Loss Basic Measurement | 0 KW to 30 KW (Three-Phase) |
Line Voltage Measurement Range | 0 KW to 866 V |
Power Factor (Inductive) Setting Range | 0 to 1 |
Phase Voltage Measurement Range | 0 V to 500 V |
Current Measurement Range | 0 A to 20 A |
Power supply voltage | 220 V ±5 V |
Power supply frequency | 50 Hz ±0.5 Hz |
No-load loss, load loss measurement maximum allowable error | ± (0.2% of the reading + 0.04% of the full scale) |
Phase voltage, line voltage measurement maximum allowable error | ± (0.2% of the reading + 0.04% of the full scale) |
Maximum allowable error of current measurement | ± (0.2% of reading + 0.04% of full scale) |
Altitude | <1.5 mi (<2500 m) |
Temperature | 50 °F to 86 °F (10 °C to 30 °C) |
Relative humidity | < 80% at 77 °F (25 °C)
|