Description
Overview
GAOTek High-Voltage Transmission Line to Ground No Voltage Tester 500kV ensures safety during maintenance by accurately detecting voltage absence. It offers reliable measurements without physical contact, minimizing risks in high-voltage environments and enhancing work efficiency.
Features
- EP8510S Wireless High-Voltage Electroscope: A fully intelligent wireless high-low voltage electroscope for power tests in high-voltage transmission lines
- Instrument Composition: Consists of a collector, expansion insulating pole, and receiver
- Detection and Testing: Detects electricity with voltage test capabilities. Allows direct contact testing up to 110 kV. Enables non-contact testing for voltages exceeding 110 kV
- Importance of Electroscope Testing: Essential for maintenance and repair of transmission lines. Checks cable voltages for safe and operable levels. Ensures operator safety by identifying residual voltage and potential leakage
- Collector and Receiver Functionality: Collector connects to a metal probe hook for easy hanging on bare wires below 110 kV, saving operator physical strength. Receiver features a 2 true color LCD screen displaying voltage level, value, and frequency
- Wireless Operation: Enables convenient testing and monitoring of electrical parameters. Provides a wireless receiving distance of approximately 100 m.
- Wide Applications: Suitable for substation, power station, railway, fire department, industrial and mining enterprises, monitoring stations, and electrical maintenance departments for electrical detection and field electric operations
Technical Specifications
Function | Wireless high voltage phase voltage, voltage to ground, voltage level, frequency, electricity test, electric field judgment |
Power | Collector: DC 3.7 V rechargeable lithium battery, full of continuous operation for about 8 hours Receiver: DC 8.4 V rechargeable lithium battery, full of continuous operation for about 8 hours |
Electro test mode | Contact: conductor voltage below 110 kV (with insulation rod) Non-contact: conductor voltage over 110 kV, close gradually (with insulation rod) |
Transmission | 433 MHz wireless |
Distance | Approx. 328.08 feet (100 m) |
Display | 3.5″ True color LCD |
Test Range | Voltage to ground: 100 V to 110 kV (50 Hz, Line to line volt multiply 1.732 |
FM (Frequency Modulation) | |
Voltage accuracy | FIY (100 V to 1000 V)
±15%±5 dgt (1 kV to 110 kV High voltage overhead lines, other application tolerance ±25%±5 dgt) |
Frequency accuracy | ±2 Hz (0.1 kV to 110.0 kV) |
Resolution | 1 V (100 V to 2000 V)
0.01 kV (2.00 kV to 20.00 kV) 0.1 kV (20.0 kV to 110.0 kV) 0.1 Hz |