Power supply |
Rechargeable lithium-ion battery pack 9.6 V, backup charger. |
Battery indicator |
Battery symbol shows dump energy. When the voltage is too low, automatic shutdown after the 1 minute. |
Power consumption |
Current consumption of normal test 490 mA, continuous working for 8 hrs. |
Display mode |
LCD color screen, 640 dots × 480 dots, 5.6 in (14.22 cm), display domain: 4.5 in × 3.46 in (116 mm × 88 mm) |
Size of clamp |
10 A small sharp current clamp: 0.29 in × 0.51 in (7.5 mm × 13 mm)100 A circle current clamp: 1.37 in × 1.57 in (35 mm × 40 mm)6000 A Flexible Coil Current Sensor (with Integrator) : 11.81 in (300 mm) |
Phase-to phase voltage |
1.0 V to 2000 V |
Phase-to-neutral voltage |
1.0 V to 1000 V |
Current |
10 A current clamp: 10 mA to 10.0 A;100 A current clamp: 0.10 A to 100 A;1000 A current clamp: 1.0 A to 1000 A;6000 A Flexible Coil Current Sensor (with Integrator) : 10 A to 6000 A |
Frequency |
40 Hz to 70 Hz |
Harmonic |
Order 0 to 50 |
Total harmonic distortion |
Order 0 to 50, each phase |
Number of Transient records |
150 sets |
Instrument dimensions |
9.44 in × 6.69 in × 2.67 in (240 mm × 170 mm × 68 mm) |
Record |
300 days (simultaneous recording 20 parameters, record one point every 5 seconds) |
Min or Max recorded value |
Measurement of maximum and minimum values over a period |
Alarm |
40 different types of parameter selections, 12,800 sets alarm logs |
Phasor diagram display |
Automatically |
Capacity of snapshots |
60 |
Automatic switching off |
When an alarm campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatic switching off. |
|
In other test mode, 15 minutes without keystrokes, automatic shutdown after prompt 1 minute. |
Backlight function |
Yes, suitable for use at night and dark place. |
Weight |
Host: 3.52 lb (1.6 kg) (with battery). |
|
Total weight: about 20.28 lb (9.2 kg) (with packaging). |
Length of voltage test wire |
9.84 ft (3 m) |
Length of current sensor wire |
6.5 ft (2 m) |
Working temperature and humidity |
50 °F to 104 °F (10 °C to 40 °C); below 80 % RH. |
Storage temperature and humidity |
50 °F to 140 °F (10 °C to 60 °C); below 70 % RH. |
Input impedance |
Input impedance of test voltage: 1 MΩ. |
Withstand voltage |
Withstand 3700 V or 50 Hz sinusoidal AC voltage for 1 minute between instrument wiring and shell. |