DC Hipot Test Kit 60kV 120kV adopts a high-frequency voltage double circuit, advanced PWM high-frequency pulse width modulation technology, closed-loop adjustment, and large voltage feedback, which greatly improves voltage stability. Use high-power IGBT devices and drive technology with superior performance, and adopt special shielding, isolation, and grounding measures according to electromagnetic compatibility theory. The Series dc high voltage generators are made of high quality, portable, and capable of withstanding rated voltage discharge without damage. It has the characteristics of large output power and small volume, reliable over-voltage, over-current, and zero-closing protection, with a 0.75 times voltage switching function. It is mainly used in the power sector, industrial and mining, metallurgy, steel, and other enterprise power departments to conduct DC withstand voltage tests or DC leakage current tests on high-voltage electrical equipment.
Features
- Series dc high voltage generators have small ripple coefficient, stable and reliable voltage output, no noise, and good reliability
- With overvoltage, overcurrent, zero voltage start and fault protection, voltage protection value can be set, display intuitive
- Voltage, current using digital display, and power supply has a reading, easy to monitor the output status
- With 0.75 times voltage conversion, easy to test zinc oxide arrester
- The product structure is compact, small size, easy to carry ant print test data.
Technical Specifications
Specifications | 200/2 | 200/3 | 200/5 | 300/2 | 300/3 |
Rated voltage) | 200 | 200 | 200 | 300 | 300 |
Rated current MA) | 2 | 3 | 5 | 2 | 3 |
Rated power) | 400 | 600 | 1000 | 600 | 900 |
Control box quality) | 5.5 | 6.0 | 6.5 | 6.5 | 6.5 |
Pressure cylinder quality) | 8.7 | 9 | 9 | 11 | 11 |
Double cylinder height mm) | (38.18 in) 970 mm | (38.18 in) 970 mm | (38.18 in) 970 mm | (49.21 in) 1250 mm | (49.21 in ) 1250 mm |
Voltage accuracy | ± (1.0%Reading + 2 words) | ||||
Current accuracy | ± (1.0%Reading + 2 words) | ||||
Ripple coefficient | ≤0.5% | ||||
Voltage stability | When the power supply voltage changes by ±10%≤1% | ||||
Overload capability | No-load voltage can exceed 10% of rated voltage for 10 minutes
The maximum charging current is 1.25 times the rated current |
||||
Power supply | Single phase communication 50 Hz 220 V±10% | ||||
Way of working | Intermittent use: rated load 30 minutes
1.1 times rated voltage usage: 10 minutes |
||||
Way of working | Relative humidity: no more than 85% at room temperature of 77 °F (25 ° C) (no condensation) | ||||
With capacitive load capacity | The tested product has unlimited capacity
Charged with 1.5 times rated current |
||||
Structural features | Electrical insulation doubler
Air insulation, no leakage |
||||
Operating box features | High-precision 0.75 UDC 1 mA one-touch button (accuracy ≤1.0%), suitable for zinc oxide lightning arrester test
Overvoltage protection using digital dial switch, briefly Portable chassis, more convenient on site |